Leave Your Message
Ngalaba Akụkọ
Akụkọ Ndị A Mapụtara

Nhazi Nhọrọ na Nchekwa nke Usoro Nhazi Ala nke 110kV Transformer Neutral Point

2026-02-13

Okwu Mmalite

Na sistemụ ike voltaji dị elu, usoro ntọala ebe na-anọpụ iche nke transformer bụ ihe dị mkpa na-emetụta nchekwa sistemụ, ntụkwasị obi, na nkwụsi ike. Maka sistemụ ike 110kV, nhọrọ nke usoro ntọala ebe na-anọpụ iche na-emetụta ọkwa mkpuchi akụrụngwa, nchebe oke voltaji, nhazi nchekwa relay, na ntụkwasị obi nke ọkọnọ ike. Na China, sistemụ 110kV na-ejikarị usoro ntọala dị irè nke na-adịghị arụ ọrụ nke ọma, ebe ụfọdụ ebe ndị na-anaghị agbanye transformer na-ada kpọmkwem ebe ndị ọzọ na-adịghị agbanye ala, na-achọ igbochi ọkụ eletrik dị mkpirikpi otu-phase ma na-egbochi ihe iyi egwu oke voltaji.

Isiokwu a na-enyocha njirimara, uru, na mmachi nke ụzọ dị iche iche e si ejikọta transformer 110kV na-anọpụ iche, na-enyocha atụmatụ nchekwa kacha mma, ma na-egosi usoro mmepe n'ọdịnihu.

Ụzọ 1 Isi Nkịtị Isi N'etiti Maka Transformers 110kV

1.1 Ịtọ ntọala ozugbo

Ịtọ ntọala ozugbona-ezo aka na njikọ kpọmkwem nke ebe na-anọpụ iche nke transformer na ụwa. Usoro a na-edozi ike isi ihe na-anọpụ iche nke ọma, na-eme ka o doo anya na n'oge nsogbu ala otu-phase, mmụba nke voltaji nke usoro na-abụghị mmejọ agaghị agafe voltaji nke usoro 1.4. Nke a na-enyere aka belata ihe achọrọ maka mkpuchi akụrụngwa ma belata ọnụ ahịa.

Agbanyeghị, otu nnukwu nsogbu bụ nnukwu nsogbu ala otu-usoro dị elu ugbu a(ruo ọtụtụ puku amperes), nke nwere ike imetụta ikike nkwụsị sekit na nkwụsi ike sistemụ. Ya mere, a na-ejikarị ntọala ozugbo eme ihe na sistemụ voltaji 110kV na sistemụ voltaji dị elu ebe ọ dị mkpa iwepụ mmejọ ngwa ngwa.

1.2 Enweghị Ala Na-anọpụ Iche

N'ime sistemụ enweghị ala, a na-ekpuchi ebe transformer na-anọpụ iche site na ụwa. Mgbe otu usoro ala nwere nsogbu, nsogbu ahụ dị obere nke ukwuu (karịsịa ike nke sistemụ ahụ), na-enye sistemụ ahụ ohere ịnọgide na-arụ ọrụ ruo obere oge (ọ na-abụkarị ruo awa abụọ). Nke a na-eme ka ọ dịkwuo mma nke ukwuu. ntụkwasị obi nke ọkọnọ ike.

Agbanyeghị, na sistemụ ndị na-enweghị ala, nsogbu ala nke otu usoro nwere ike ime ka voltaji nke usoro na-abụghị nke nwere nsogbu rịgoro ruo ọkwa voltaji ahịrị. Ọ bụrụ na mkpuchi ahụ adịghị ike, nke a nwere ike ibute mmebi, na-abawanye ruo na nsogbu nke usoro ruo na nke usoro. Na mgbakwunye, ntọala arc nke na-agafe agafe nwere ike ịmepụta voltaji arc karịrị arc, na-eru okpukpu 3–3.5 nke voltaji nke usoro ahụ, na-etinye ihe iyi egwu na mkpuchi transformer.

1.3 Ịtọ ntọala site na obere ihe mgbochi

Iji mee ka uru na ọghọm nke sistemụ ntọala kpọmkwem na nke na-enweghị ala dị mma, usoro ntọala impedancea na-ejikarị eme ihe. Nke a gụnyere ịkụda ala site na obere iguzogide ma ọ bụ obere mmeghachi omume.

  • Obere Nguzogide Ala: Na-ebelata nsogbu ruo ọtụtụ narị amperes, na-ebelata mmetụta na sistemụ ahụ ma na-eme ka ọrụ nchekwa ngwa ngwa dị. Usoro a na-egbochi oke voltaji nke ọma ma dabara adaba maka netwọk nkesa nke eriri nwere nnukwu ọkụ eletrik.
  • Obere Ndabere Mmeghachi Omume: Nwere ike ịgbanwe ike capacitive nke sistemụ ahụ site na inductive current, na-ebelata ohere nke arc rejunction. A na-ewerekarị usoro a dị ka usoro ntọala akwụgoro ụgwọ.

Iji obere impedance grounding na-ejikọta uru nke sistemụ kpọmkwem na nke na-enweghị ala, na-enye nkwụsịtụ oke voltaji na ntụkwasị obi dị elu nke ọkọnọ ike. A na-ejikarị ya eme ihe n'ọtụtụ ebe na sistemụ 110kV, ọkachasị ndị nwere nnukwu ọkụ eletrik ma ọ bụ ndị chọrọ ike dị elu.

Nhazi Nchedo 2 maka Isi Ihe Mgbanwe 110kV

2.1 Ihe iyi egwu oke voltaji

Ọkwa mkpuchi nke ebe na-anọpụ iche nke transformer 110kV na-abụkarị nke a na-ahụkarị. ọkara mkpuchi, yana ọkwa voltaji na-eguzogide naanị otu ụzọ n'ụzọ atọ nke njedebe ahịrị. Nke a na-eme ka ebe na-anọpụ iche ghara ịdị mfe maka mmebi oke voltaji. Ụdị oke voltaji bụ isi gụnyere:

  • Oke voltaji ugboro ole ike: Site na mgbanwe ahịrị, sekit dị mkpụmkpụ na-adịghị agbanwe agbanwe, ma ọ bụ mfu ibu mberede.
  • Oke voltaji Resonance: Ọ bụ mgbanwe sitere na mmekọrịta dị n'etiti ihe ndị na-akpali akpali na ndị na-eme ka ike dị n'oge ọrụ sistemụ ma ọ bụ mmejọ.
  • Mgbanwe Overvoltaji: Nke sitere na mgbanwe nke ike magnetik na electrostatic n'oge mmeghe ma ọ bụ mmechi nke ihe mgbawa sekit.
  • Voltaji karịrị akarị nke àmụmà: Ọ bụ site na mgbawa àmụ̀mà, nke a na-amata site na oke olu na obere oge.

2.2 Ngwaọrụ Nchedo Ndị A Na-ahụkarị

Iji chebe ebe na-anọpụ iche nke transformer, a na-ejikarị ngwaọrụ nchebe ndị a:

  • Ndị Na-ejide Mberede: Ihe ndị a na-egbochi oke voltaji àmụ̀mà na ụfọdụ oke voltaji mgbanwe. Agbanyeghị, ihe njide mmụba ọkọlọtọ anaghị adịkarị mma maka obere ọkwa mkpuchi nke isi ihe na-anọpụ iche nke transformer 110kV, na-eme ka nhọrọ sie ike.
  • Oghere NnọpụicheIhe ndị a na-echebe megide ugboro ike na oke voltaji resonance. Mgbe oke voltaji mere, oghere ahụ na-agbaji, na-eme ka ebe na-anọpụ iche ghara ịdị irè iji belata mmụba voltaji. Ihe na-adịghị mma bụ nsogbu dị na ịhazi anya oghere ahụ nke ọma, nke nwere ike ibute enweghị nhazi nchekwa.
  • Njikọ Yiri nke Ihe Mgbochi Mkpọchi na Oghere: Nke a bụ ụzọ nchekwa a na-ejikarị eme ihe. Ihe njide ọkụ na-ejikwa oke voltaji àmụ̀mà, ebe oghere ahụ na-eleba anya na ugboro ike na oke voltaji resonance. Oghere ahụ na-echekwa ihe njide ọkụ ahụ site na oke voltaji ike nke nwere ike ibute ọdịda ya. Ụzọ a na-enye uru ndị ọzọ.

2.3 Nhazi Nchedo Relay

Nchedo relay maka ebe na-anọpụ iche nke transformer 110kV gụnyere akụkụ ndị a:

  • Nchedo Ugbu a Na-enweghị Usoro: Maka transformers ndị a na-agbanye n'ala ozugbo, a na-ahazi nchedo ọkụ eletrik efu ka ọ wepụ nsogbu ala ngwa ngwa. A na-ekewakarị nchedo ahụ n'ime ngalaba, yana obere oge igbu oge maka ebe mmejọ dị na ya na ogologo oge igbu oge maka ịkwụsịtụ akụkụ niile nke transformer ahụ.
  • Nchedo Voltaji efu na Nchedo Ugbu a: Maka transformers na-enweghị ala, a na-etinye nchedo voltaji efu na nchedo ugbu a oghere. Mgbe nsogbu ala mere ka sistemụ ahụ tụfuo isi ala ya, nke na-eduga na mmụba voltaji isi na-anọpụ iche, oghere ahụ na-agbaji. Nchedo ugbu a oghere ma ọ bụ nchedo voltaji efu na-arụ ọrụ na igbu oge (0.3–0.5s) iji chụpụ transformer ahụ n'akụkụ niile.
  • Nhazi Nchekwa Ndabere: Iji hụ na nhọrọ dị, a ga-ahazi oge nchekwa efu-usoro. Dịka ọmụmaatụ, oge igbu oge maka nchekwa ndabere na transformer kwesịrị ịdị ogologo karịa nke nchekwa ahịrị ọ na-akwado.

3 Atụmatụ Nhazi na Nyocha Ikpe

3.1 Mmachi nke Ụzọ Omenala

Mgbe a na-eji ihe njide mmụba yiri oghere ndị yiri yaỌ bụ ihe a na-ahụkarị, usoro a nwere ọtụtụ adịghị ike:

  • Ihe isi ike na nhọrọ nke onye njide Surge: Ọ na-esiri ike ịchọta ihe njide elu ọkọlọtọ nke na-emezu ihe achọrọ nke ma voltaji ọrụ dị elu na-aga n'ihu na obere voltaji fọdụrụnụ nke àmụ̀mà maka isi ihe na-anọpụ iche nke transformer 110kV.
  • Ihe ịma aka dị na Nhazi Oghere: Voltaji mgbawa oghere ikuku nwere ike ịgbasa, nke na-eme ka o sie ike ịhazi ọrụ oghere maka "mfu ala" na "na ọnọdụ ntụpọ ala".
  • Mgbagwoju anya nke Nchedo Relay: Nchedo megide "mfu ala" (dịka oke voltaji efu na nchedo oke oghere) nwere ike imebi ọrụ, na-achọ ihe mgbochi ndị ọzọ, nke na-eme ka mgbagwoju anya dịkwuo elu ma na-ebelata ntụkwasị obi.

3.2 Uru nke ịkụ ala site na obere mmeghachi omume

Nnyocha na omume na-egosi na ịtọ ntọala ebe na-anọpụ iche site na obere mmeghachi omumena-enye uru dị ukwuu karịa usoro ntọala akụkụ ọdịnala:

  • Mbelata ọkwa mkpuchi ihe achọrọ: Mgbe ejiri obere ntọala reactance mee ihe, enwere ike ibelata ọkwa mkpuchi nke ebe na-anọpụ iche nke transformer site na 35kV ruo 20kV, na-egbochi mkpa maka njide elu na oghere ma na-eme ka nhazi nchebe dị mfe.
  • Ụdị Njikota Ala Dị n'Otu: Usoro a na-ewepụ ihe na-eme ka sistemụ na-enweghị ala dị iche, na-enye ohere ka ọ dị mfe ma ọ bụ wepụ nchedo metụtara ya, si otú a na-eme ka ntụkwasị obi dịkwuo elu.
  • Njide nke Uru: Ọ na-ejigide uru nke ime ka ala dị n'ime ala, dịka nchekwa dị mfe ma a pụrụ ịtụkwasị obi na usoro efu, ebe ọ na-egbochi ọkụ eletrik dị mkpụmkpụ nke otu usoro.

3.3 Nyocha Ọmụmụ Ihe

Ihe atụ bụ mgbanwe ọdụ ụgbọ ala 110kV. Nhazi mbụ ahụ jiri ihe njide mmụba yiri ogheremaka nchebe ebe na-anọpụ iche. Agbanyeghị, mgbe ejiri obere ntọala reactance mee ihe, ọkwa mkpuchi achọrọ nke ebe na-anọpụ iche nke transformer belatara, e mere ka ngwaọrụ nchebe dị mfe, ma melite ntụkwasị obi ọrụ. Ngụkọta ego gosiri na iguzogide ala nwere ike ibelata nsogbu ahụ ruo narị amperes ole na ole, a pụkwara ịhazi nchedo usoro efu ngwa ngwa.

Ikpe ọzọ metụtara nsogbu dị na obere ọdụ 110kV ebe nsogbu ala nke otu-phase dị n'ahịrị na-abata butere mmebi oghere ebe na-anọpụ iche na mgbanwe transformer. Nnyocha gosiri na ọ bụ ezie na nsogbu ahịrị ahụ bụ nke nwa oge, nzaghachi sitere na ọtụtụ injin asynchronousn'akụkụ ibu nyere ike maka arc ahụ, na-akwado nsogbu ahụ. Nke a na-eme ka ọ pụta ìhè na maka transformers nwere ibu moto dị mkpa (isi mmalite ndị yiri ya), nchebe ebe na-anọpụ iche zuru oke, gụnyere oke ọsọ nke usoro efu, ọkụ oghere, na nchekwa voltaji nke usoro efu, dị mkpa n'oge nhazi.

Mmechi na Echiche nke 4

Ịhọrọ usoro ntọala nke transformer 110kV na-anọpụ iche na nhazi nchekwa ya bụ ọrụ dị iche iche nke chọrọ ịtụle nhazi sistemụ, njirimara ibu, na ihe achọrọ maka ntụkwasị obi. Ọ bụ ezie na usoro ntọala akụkụ ọdịnala yana ihe njide elu na oghere bụ ihe a na-ahụkarị, ọ na-eche nsogbu ihu na nhọrọ ngwaọrụ na nhazi nhazi. obere usoro ịkụda ihe mmeghachi omumena-enye ụzọ ọzọ dị mma, nke nwere ike ibelata ihe achọrọ maka mkpuchi, ime ka nchebe dị mfe, ma melite ntụkwasị obi.

Usoro mmepe n'ọdịnihu ga-elekwasị anya n'akụkụ ndị a:

  • Ojiji nke Ngwaọrụ ỌhụrụDịka oghere ndị mejupụtara ma ọ bụ oghere ndị a na-achịkwa nke ejiri ya na ihe njide ebili, na-eme ka nchekwa dịkwuo mma ma na-eme ka ọ dị mfe ịtụkwasị obi.
  • Teknụzụ Nchedo Dijitalụ: Iji nchekwa dabere na kọmputa site na iji algọridim dị elu (dịka ọmụmaatụ, njirimara waveform, nyocha harmonic) iji melite mmetụta na ntụkwasị obi nke nchekwa nsogbu ala.
  • Nhazi na NhaziỊmepụta ngwa nchekwa ebe a na-ahazi nke ọma na nke modular iji mee ka imewe na mmezi dị mfe.

Na nchịkọta, imeziwanye usoro ntọala nke transformer 110kV na nhazi nchekwa dị oke mkpa maka ime ka nchekwa, ntụkwasị obi, na ọrụ akụ na ụba nke sistemụ ike dịkwuo mma. Site na mmepe teknụzụ, a na-atụ anya na ngwọta ndị nwere ọgụgụ isi na nke dị irè ga-apụta ma nweta ojiji zuru oke.