+86 18068001229 Oghere Mkpuchi Isi nke Transformer Inter-Coil 220kV: Nyocha na Atụmatụ Mmezi Ọhịa Eletriki
Okwu Mmalite
N'ihe gbasara nnyefe ike voltaji dị elu, transformers 220kV na-arụ ọrụ dị oke mkpa n'ịhụ na ekesara ike nke ọma. isi mkpuchi ogheren'etiti winding transformer na-anọchite anya otu n'ime ihe ndị kacha mkpa e ji emepụta ihe, na-emetụta ntụkwasị obi nke transformer, ogologo oge, na arụmọrụ ya ozugbo. Dịka ndị isi ahịa na teknụzụ transformer, anyị ghọtara na nhazi mkpuchi kacha mma dị oke mkpa iji nagide nrụgide eletriki dị oke njọ, gụnyere voltaji ọrụ na-aga n'ihu, mkpali àmụ̀mà, na mgbanwe mmụba.
Isiokwu a na-enyocha ụzọ nyocha ubi eletriki dị elu na atụmatụ mmezi bara uru maka oghere mkpuchi isi transformer 220kV inter-coil. Site na iji teknụzụ simulation dị elu na ụkpụrụ imewe ọhụrụ, anyị nwere ike ime ka arụmọrụ mkpuchi transformer dịkwuo mma, na-ahụ na ọrụ ya dị mma n'ebe kachasị mkpa.
Isi ihe dị mkpa nke mkpuchi isi na transformers 220kV
Isi oghere mkpuchi dị n'etiti windings na transformers 220kV na-eje ozi dị ka ihe mgbochi dielectric bụ isi, na-egbochi mmebi eletriki n'etiti coils voltaji dị elu na obere voltaji. Sistemụ mkpuchi a aghaghị iguzogide ọ bụghị naanị ọnọdụ ọrụ ọkọlọtọ kamakwa ọtụtụ ọnọdụ dị iche iche. ọnọdụ overvoltagenke na-eme n'oge nsogbu grid.
Na ngwa 220kV, oghere mkpuchi na-ejikarị sistemụ ọtụtụ ihe mgbochinke nwere silinda ma ọ bụ ihe mkpuchi nke na-ekewa oghere ahụ n'ime ọtụtụ obere ọkpọkọ mmanụ. Ụzọ a na-eme ka ọ dịkwuo mma nke ukwuu. voltaji mmalite mwepụta nke akụkụ(PDIV) ma gbochie mmepụta nke àkwà mmiri ndị na-adịghị ọcha n'etiti windings. Nhazi bụ isi na-agbaso ụkpụrụ "tube akwụkwọ dị gịrịgịrị, obere oghere mmanụ", ebe ebe ihe mgbochi na-adịkarị ọkpụrụkpụ 2mm, oghere mmanụ dị n'etiti ihe mgbochi dị site na 6 ruo 10mm.
Nkesa ọkụ eletrik n'ime oghere ndị a abụghị otu, mana oke nrụgidena-eme n'akụkụ gbagọrọ agbagọ, mgbagọ ndị na-eduzi ihe, na njikọ mkpuchi. Na-enweghị nhazi nhazi kwesịrị ekwesị, ebe ndị a nwere nrụgide dị elu nwere ike ịmalite ọrụ mwepụ akụkụ nke ihe, na-eduga na mmebi mkpuchi na-aga n'ihu na ọdịda nwere ike ime.
Usoro Nyocha Ọgbọ Eletriki
Usoro Mmepụta Ihe (FEM)
Nhazi mkpuchi nke oge a dabere nke ukwuu na nyocha ihe nwere njedebe(FEA) maka nhazi ọkụ eletrik ziri ezi. Site n'ikewa geometry mkpuchi n'ime puku kwuru puku ihe dị iche iche, FEM nwere ike ịgbakọ nkesa nwere ike imena ike ubina izi ezi dị egwu. Maka transformers 220kV, nyocha a na-elekwasịkarị anya na mpaghara atọ dị mkpa: mkpuchi elu njedebe, ngalaba etiti n'etiti windings, na mkpuchi njedebe dị ala.
Ihe nlereanya anyị na-ekpughe na ike ọkụ eletrik kachasị elu na transformers 220kV na-emekarị na mpaghara ebe ọkụ eletrik dị. nkuku elu dị n'imenke windings voltaji dị elu, karịsịa nso na akụkụ njedebe ahịrị. N'oge ule mkpali àmụ̀mà (1050kV maka sistemụ 220kV), mpaghara ndị a nwere ike ịnweta ike ubi karịrị 8-9kV/mm, na-eru nso oke mmebi nke ihe mkpuchi.
Nchọpụta nke Mpaghara Nrụgide Dị Mkpa
Site na nyocha zuru oke nke ubi eletriki, anyị achọpụtala ọtụtụ mpaghara nrụgide dị mkpa chọrọ nlebara anya pụrụ iche na transformers 220kV:
- Mpaghara nsọtụ na-agbanwe agbanwe: Nkuku dị nkọ na nsọtụ gbagọrọ agbagọ na-emepụta oke mkpokọta ubi, nke chọrọ usoro nhazi pụrụ iche.
- Njikọ dị n'etiti mkpuchi siri ike na mmiri mmiriNjirimara dielectric dị iche iche nke pressboard na mmanụ na-eme ka ubi sie ike na njikọ ha.
- Ebe ndị mmadụ si apụ apụ: Ebe mgbanwe ebe ndị nwere ike ịnweta voltaji dị elu na-apụ na windings na-enye nkesa ubi siri ike karịsịa nke chọrọ nyocha akụkụ atọ.
Maka transformers 220kV, ike kachasị elu nke ubi eletriki na-emekarị na diski ole na ole mbụ dị nso na njedebe ahịrị na ebe njikọ dị n'etiti diski ndị dị n'etiti na diski nkịtị n'oge ọnọdụ mkpali. Ebe ndị a chọrọ usoro mkpuchi ka mma iji gbochie ọdịda tupu oge eruo.
Atụmatụ Mmezi Maka Oghere Mkpuchi Isi
Nhazi Jiọmetrịka
Ịkpụzi elektrọdna-anọchite anya otu n'ime atụmatụ kachasị dị irè maka imeziwanye nkesa ubi. Site n'iji nkuku dị nkọ dochie akụkụ dị nkọ na profaịlụ gbagọrọ agbagọna itinye n'ọrụ elektrọd toroidal, anyị nwere ike ibelata ike kachasị elu nke ubi site na ruo 30-40%. Maka transformers 220kV, nke a gụnyere:
- Mgbaaka njedebe kwụ ọtọ(SER) na ọdụ ndị na-agbagharị agbagharị iji mepụta gradients nwere ike ịdị nro.
- Mgbaaka nkukuyana profaịlụ nke na-eme ka ahịrị ngwa ngwa dị, na-ebelata nrụgide tangential nke ukwuu n'elu pressboard.
- Cones nrụgidena njikọ dị mkpa iji chịkwaa ọdịiche dị n'ọhịa ma belata njupụta.
Oke nke nhazi mgbagọ dị oke mkpa - ịbawanye radius nkuku nke ndị na-eduzi na mgbanaka kwụ ọtọ nwere ike ibelata ike ubi nke ukwuu (ike ubi ∝ 1/radius).
Ihe mkpuchi dị elu
Nhọrọ ihe dị mkpa na-arụ ọrụ dị mkpa n'ịkwalite arụmọrụ mkpuchi. Transformers 220kV anyị na-eji:
- Igwe ntinye aka dị eluna-eme ka akụkụ kwụsie ike nke ọma na ike dielectric dị elu.
- Akwụkwọ emelitere n'oge okpomọkụnke na-enye ntachi obi okpomọkụ dị elu, na-ejigide ihe onwunwe dielectric na okpomọkụ dị elu.
- Ihe ndị e ji mee ka Nanocomposite dịkwuo mmaebe a na-etinye nanoparticles (SiO₂, Al₂O₃) na epoxy ma ọ bụ mmanụ na-eme ka ike dielectric dịkwuo mma site na 20-30% ma na-eme ka ike okpomọkụ dịkwuo mma.
Ihe ndị a dị elu na-enye ohere maka imepụta ihe mkpuchi dị obere ma na-edozi ma ọ bụ ọbụna na-eme ka akụkụ ntụkwasị obi dịkwuo mma. Dịka ọmụmaatụ, itinye usoro mkpuchi nanocomposite nwere ike ịgbatị ndụ mkpuchi site na 20-30% ma e jiri ya tụnyere ihe ndị a na-ahụkarị.
Nhazi Sistemụ Mkpuchi
Nhazi anụ ahụ nke ihe mkpuchi na-eme ka ihe ndị dị na ya dịkwuo mma:
- Sistemụ mkpuchi ọkwaebe ọkpụrụkpụ mkpuchi na-agbanwe dịka nkesa voltaji si dị n'akụkụ winding ahụ.
- Nhazi nhazi ihe mgbochisite na iji nyocha FEM iji chọpụta ọnọdụ kacha mma nke pressboard nke na-ebelata nrụgide kachasị elu nke oghere mmanụ.
- Nhazi ọwara mmanụnke na-ahazi ihe achọrọ maka eletriki (obere oghere maka PDIV dị elu) na mkpa oyi (oke mmanụ).
Maka transformers 220kV, anyị achọpụtala nke ahụ usoro ịgbagharị agbagọ dị iche icheSite na pasentị ndị na-ahapụ ihe karịrị 65-70%, ọ na-eme ka nkesa voltaji mkpali dịkwuo mma nke ukwuu, na-ebelata nrụgide na diski ole na ole mbụ ruo 50% ma e jiri ya tụnyere atụmatụ ọdịnala.
Ọmụmụ Ihe: Mmejuputa nke Ọma na Transformer 220kV
Ọrụ anyị nke na-eme n'oge na-adịbeghị anya nke gụnyere transformer 220kV dị elu na-egosi irè nke atụmatụ mmezi ndị a. Nhazi mbụ ahụ gosiri oke oke ike ọkụ eletrik (ruo 9.5kV/mm) n'ime oghere mkpuchi isi dị n'etiti windings dị elu na obere voltaji, karịsịa nso nsọtụ winding.
Site na nyocha FEM ugboro ugboro site na iji ngwanrọ pụrụ iche (HSSSM), anyị tinyere ngwugwu mmezi zuru oke:
- Mgbaaka electrostatic emegharịrị ọhụrụna nhazi na nhazi kachasị mma.
- Mgbaaka nkuku ndị ọzọna nsọtụ nke na-agbagharị iji kewaa olu mmanụ ma melite ike nke na-agbagharị agbagharị.
- Nhazi ihe mgbochi emezigharịrịimepụta obere oghere mmanụ dị iche iche (6-8mm) kama oghere ndị buru ibu mbụ (12-15mm).
Nsonaazụ ya dị oke mma: ike ubi kachasị elu ebelatara ruo 6.2kV/mm (mmezi 35%), yana nkesa ubi ka mma n'ofe usoro mkpuchi ahụ. Transformer agbanwere agbanwe gafere ule niile a na-eme kwa ụbọchị na ụdị, gụnyere ule ike iguzogide ugboro ugboro (460kV maka nkeji 1) na ule ọkụ (1050kV), yana ọkwa mwepụta akụkụ na-erughị 10pC mgbe niile.
Ntụle Mmepụta na Ịdị Mma
Ọbụna imewe kachasị elu anaghị arụ ọrụ nke ọma ma ọ bụrụ na enweghị njikwa nrụpụta kwesịrị ekwesị. Mmemme nkwenye ogo anyị maka mkpuchi transformer 220kV gụnyere:
- Njikwa usoro ọnụọgụgụn'oge a na-emepụta pressboard na nchikọta ihe.
- Ịkpọcha ihe mkpofu na itinye mmanụ n'ime iheusoro ndị na-eme ka e wepụ mmiri na gas kpamkpam nke nwere ike ibute mwepụ akụkụ.
- Maapụ mwepụ nke akụkụn'oge ule mkpali iji chọpụta ma dozie ezughị okè nrụpụta ọ bụla.
Maka transformers 220kV, anyị na-etinye usoro nhicha siri ike n'oge mgbakọ na mwepụ na ọrụ tankị, ebe ọ bụ na ọbụna ihe ndị na-emerụ emerụ nwere ike ibelata ike mkpuchi nke ukwuu n'okpuru ọkụ eletrik dị elu.
Usoro Ọdịnihu na Teknụzụ Mkpuchi
Mgbanwe nke mkpuchi transformer na-aga n'ihu na ọtụtụ mmepe dị mma:
- Teknụzụ ejima dijitalụimepụta ihe ndị mebere emebere nke sistemu mkpuchi maka nlekota arụmọrụ n'oge na mmezi amụma.
- Nlekota ọnọdụ dị eluiji ihe mmetụta eriri optic agbakwunyere iji soro ọrụ mwepụta akụkụ na ebe okpomọkụ dị n'oge ọrụ transformer ahụ.
- Mmiri mkpuchi na gburugburu ebe obibidịka esters eke na-enye ebe ọkụ dị elu na mmekorita gburugburu ebe obibi ka mma ebe a na-ejigide arụmọrụ dielectric.
Maka ngwa 220kV, obi dị anyị ezigbo ụtọ maka ya ngwa mmụta igwena nhazi nhazi mkpuchi, ebe algọridim nwere ike inyocha ọtụtụ puku mgbanwe nhazi ngwa ngwa iji chọpụta nhazi kachasị mma nke na-edozi ihe gbasara eletriki, okpomọkụ, na akụ na ụba.
Mmechi
Nhazi nke oghere mkpuchi isi nke transformer 220kV inter-coil na-anọchite anya ihe ịma aka injinia dị elu nke chọrọ ihe ọmụma miri emi nke ozizi dielectric, ikike ịme ihe atụ dị elu, na ahụmịhe nrụpụta bara uru. Site na nyocha ubi eletriki zuru oke na atụmatụ mmezi ezubere iche, anyị nwere ike ime ka ntụkwasị obi transformer na ogologo ndụ dịkwuo mma.
Usoro anyị na-egosi na nhazi mkpuchi atụmatụ abụghị naanị na ọ na-eme ka arụmọrụ dielectric ka mma kamakwa ọ na-eme ka transformers dị obere ma dị ọnụ ala karịa. Site n'itinye usoro ndị a dị elu n'ọrụ, anyị na-enye transformers ndị gafere ọkọlọtọ ụlọ ọrụ ebe anyị na-enye ndị ahịa anyị ntụkwasị obi arụmọrụ ka mma na ọnụ ahịa zuru oke nke uru nke onye nwe ha.
Ka teknụzụ na-aga n'ihu na-agbanwe, anyị na-agba mbọ itinye aka na mmepe kachasị ọhụrụ na nhazi mkpuchi, na-eme ka ndị ahịa anyị rite uru site na ngwọta transformer kachasị ntụkwasị obi na nke dị irè dị na ahịa.
Kpọtụrụ ndị otu injinia anyị taaiji kparịta otu ọkachamara anyị pụrụ iche maka imepụta mkpuchi nwere ike isi mee ka arụmọrụ na ntụkwasị obi nke ọrụ transformer 220kV gị ka mma.